| MKS/TKS-Relay |
| MKS/TKS with
relay or SSR output selectable |
| - Output
failure detection alarm with load current measurement (OFD function).
|
| - 2 programmable
setpoints (main and auxiliary). |
| |
Outputs |
| Type: time proportioning |
| Action: direct/reverse keyboard programmable |
| Main output cycle time: programmable
from 1 to 200 seconds |
| Secondary output cycle time:programmable
from 1 to 200 seconds |
| |
Output 1 relay
|
| Note:for Output 1 only, the relay output
and SSR output are both fitted and the output to be used is selected
by jumper |
| Function:control output (heating) |
| Relay type: SPST. NO or NC contact is
selected by jumper |
| Contact rating:3 A @ 250 Vac on resistive
load |
|
Output 1 SSR |
- Logic
level 1: 14 Vdc ±20% @ 20 mA max.
24 Vdc ±20% @ 1 mA max. |
| - Logic level
0: < 0.5 Vdc. |
| |
Output 2 and 3
|
| Type:relay with SPST contact |
| Contact rating:2 A @ 250 Vac on resistive
load. |
| |
Output 4 (optional
alarm 3 output) |
| Type: relay with SPST contact |
| Contact rating:2 A @ 250 Vac on resistive
load |
| MKS/TKS-mA |
| MKS/TKS-mA
with linear output |
| - One linear
output (mA) programmable as control output or analog retransmission
of the measured value or operating setpoint. |
| - 4 local
setpoints selectable by logic inputs. |
| - 24 Vdc
auxiliary power supply. |
| |
Outputs |
| Action: direct/reverse keyboard programmable |
| Main output cycle time:programmable
from 1 to 200 seconds |
| Secondary output cycle time: programmable
from 1 to 200 seconds |
| |
Output 1 |
| Type: opto-isolated 0-20 mA or 4-20
mA |
| Function: Programmable as: |
| - Control
output (heating or cooling) |
| - Retransmission
of the measured value |
| - Retransmission
of the operating setpoint |
| Scaling: programmable from -1999 to
4000 |
| Maximum load: 500 W |
| Resolution: 0.1% when used as control
output; 0.05% when used as analog retran |
| Digital filter: on the output retransmission
(same time constant as readout) |
| Output level indication: (as control
output only) from 00.0 to 100.0% |
| Output status indication: the OUT 1
indicator flashes with a duty cycle proportional to the output level |
| |
Output 2 Relay
|
| Note: for Output 2 only, the relay output
and SSR output are both fitted, and the output used is selected by
jumper |
| Function: control output (heating) |
| Relay type: SPST. Contact NO or NC selectable
by jumper |
| Contact rating: 3 A @ 250 Vac on resistive
load |
| |
Output 2 SSR |
| - Logic level
1: 14 Vdc ±20% @ 20 mA max |
| 24 Vdc ±20%
@ 1 mA max |
| - Logic level
0: < 0.5 Vdc |
| |
Output 3 |
| Type: relay with SPST contact |
| Function: control output or alarm 2
output |
| Contact rating: 2 A @ 250 Vac on resistive
load |
| |
Output 4 (optional
alarm 3 output) |
| Type: relay with SPST contact |
| Contact rating: 2 A @ 250 Vac on resistive
load |
| MKS/TKS
- Servo |
| For MKS/TKS-Servo
with servomotor control output |
| - 4 local
setpoints selectable by logic inputs |
| - AUTO/MANUAL
transfer with programmable valve positioning |
| |
Outputs |
| Action:direct/reverse keyboard programmable |
| Main output cycle time: programmable
from 1 to 200 seconds |
| Secondary output cycle time: programmable
from 1 to 200 seconds |
| |
Output 1 and 2
servomotor |
| Type: 2 interlocked relays(Open/Closed) |
| Relay:SPST contact (NO) |
| Contact rating: 3 A @ 250 Vac on resistive
load |
| |
Output 1 Relay |
| Function:control output |
| Relay type:SPST. NO or NC selectable
by jumper |
| Contact rating: 3 A @ 250 Vac on resistive
load |
| |
Output 3 |
| Type:relay with SPST contact |
| Contact rating: 2 A @ 250 Vac on resistive
load |
| |
Output 4 (optional
alarm 3 output) |
| Type:relay with SPST contact |
| Contact rating:2 A @ 250 Vac on resistive
load |
| |
Control output |
| A) Closed
loop Feedback |
| Potentiometer range: from 100 Wto 10KW |
| Servomotor deadband: from 1% to 50%
of the selected stroke time |
| Control action:direct or reverse programmable |
| Valve position limiter: low and high
limiters programmable |
| B) Open loop servomotor with valve position
Indication |
| Potentiometer range: from 100W
to 10KW |
| Servomotor deadband: from 1% to 50%
of the selected stroke time |
| Servomotor stroke time: programmable
from 6 seconds to 3 minutes |
| Control action:direct or reverse programmable |
| C) Open loop servomotor without valve position
indication |
| Servomotor deadband: from 1% to 50%
of the selected stroke time |
| Servomotor stroke time: programmable
from 6 seconds to 3 minutes |
| Control action: direct or reverse programmable |
| D) One time proportioning output |
| Output used: output 1 |
| Control action: direct or reverse programmable |
| Output cycle time: from 1 to 200 seconds |
| Output power limiting: high limit programmable |
| E) Two time proportioning outputs |
| Outputs used: outputs 1 and 3 |
| Output cycle time: from 1 to 200 seconds |
| Output power limiting: high limit programmable |